Add to Cart
Siemens 6EP1 437 3BA00 Power Supply Input 400-500 V 3 AC Output: 24 V DC/40 A Notes
Details of 6EP1 437 3BA00
Article Number (Market Facing Number) 6EP1437-3BA00
Product Description SITOP modular 40 A stabilized power supply input: 400-500 V 3 AC output: 24 V DC/40 A
Product family Ordering Data Overview
Product Lifecycle (PLM) PM400:Phase Out Started
PLM Effective Date Product phase-out since: 01.10.2014
Input
Data sheet 6EP1437-3BA00
SITOP MODULAR/3AC/24VDC/40A
SITOP modular 40 A Stabilized
power supply input: 3 AC 400-
500 V output: 24 V DC/40 A
Input
Input 3-phase AC
Rated voltage value Vin rated 400 ... 500 V
Voltage range AC 320 ... 550 V
● Note Starting from Vin > 340 V
Wide-range input Yes
Overvoltage resistance 2.3 × Vin rated, 1.3 ms
Mains buffering at Vin = 400 V
Mains buffering at Iout rated, min. 6 ms; at Vin = 400 V
Rated line frequency 1 50 Hz
Rated line frequency 2 60 Hz
Rated line range 47 ... 63 Hz
input current
● at rated input voltage 400 V 2.2 A
Switch-on current limiting (+25 °C), max. 70 A
I²t, max. 2.8 A²·s
Built-in incoming fuse none
Protection in the mains power input (IEC 898) Required: 3-pole connected miniature circuit breaker 10 ... 16 A
characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or
3RV2711-1DD10 (UL 489
Output
Controlled, isolated DC voltage
Rated voltage Vout DC
24V
Total tolerance,static ±
3%
Static mains compensation, approx.
0.1%
Static load balancing, approx.
0.2%
Residual ripple peak-peak, max.
100 mV
Spikes peak-peak, max. (bandwidth:20 MHz)
200 mV
Adjustment range
24...28.8V
product function output voltage adjustable
Yes
Output voltage setting
via potentiometer; max.960 W
Status display
Green LED for 24 V OK
Signaling
via signaling module(6EP1961-3BA10)
On/off behavior
No overshoot of Vout (soft start)
Startup delay, max.
2.5 s
voltage increase time of the output voltage maximum
Rated current value Iout rated 40 A
Current range 0 ... 40 A
● Note +60 ... +70 °C: Derating 2%/K
supplied active power typical 960 W
short-term overload current
● at short-circuit during operation typical 120 A
duration of overloading capability for excess current
● at short-circuit during operation 25 ms
constant overload current
● on short-circuiting during the start-up typical 46 A
Parallel switching for enhanced performance Yes; switchable characteristic
Numbers of parallel switchable units for enhanced
performance
2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 90 %
Power loss at Vout rated, Iout rated, approx. 106 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max. 1 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. 2 %
Load step setting time 50 to 100%, typ. 4 ms
Load step setting time 100 to 50%, typ. 4 ms
setting time maximum 10 ms
Protection and monitoring
Output overvoltage protection < 35 V
Current limitation, typ. 46 A
property of the output short-circuit proof Yes
Short-circuit protection Alternatively, constant current characteristic approx. 46 A or latching
shutdown
enduring short circuit current RMS value
● typical 46 A
Overload/short-circuit indicator LED yellow for "overload", LED red for "latching shutdown"
OTHER SUPERIOR PRODUCTS
Yasakawa Motor, Driver SG- | Mitsubishi Motor HC-,HA- |
Westinghouse Modules 1C-,5X- | Emerson VE-,KJ- |
Honeywell TC-,TK- | GE Modules IC - |
ABB Module | AB Module 1756-,1759- Tourch Screen 2711- |
Mitsubishi Drive MR- , Motor HA -,HC | Emerson MoudlesVE- ,KJ - |
Fanuc motor A0-, Drive | Yokogawa transmitter EJA- |
Rosemount Transmitter 3051- | Schneider Module 140- |
Panasonic Motor , Drive MH- | Siemens Module 6ES-, Touch Screen 6AV- |
FAQ
Q1. What about the lead time?
A: 3-5 days for Sample preparing ,8-10 working days for mass production.
Q2. Do you have any MOQ limit of Industrial Servo Drives?
A: Low MOQ, 1pc is available.
Q3. How do you ship the goods and how long does it take to arrive?
A: Ship by DHL, UPS, FedEx or TNT. It takes 3-5 days to arrive. Airline and sea shipping also optional.
Secondly, during the guarantee period, we will send new lights with new order for small quantity. For defective batch products, we will repair them and resend them to you or we can discuss the solution including re-call according to real situation.